Add report functionality to output the calculation results
This commit is contained in:
@@ -0,0 +1,77 @@
|
|||||||
|
from coefficients import RHO_CP_AIR
|
||||||
|
from ventilation import Room
|
||||||
|
from interfaces import Interface, Surface
|
||||||
|
|
||||||
|
|
||||||
|
def infiltration_losses(area, v50, reduction_factor=20):
|
||||||
|
# TODO: review factor 20 vs factor 25 reduction. I think factor 20 is used for
|
||||||
|
# dimensioning the required input and 25 for average use calculations
|
||||||
|
|
||||||
|
# Infiltration losses
|
||||||
|
flow_rate = (v50 / reduction_factor) * area / 3600 # m^3 / s
|
||||||
|
HV_inf = RHO_CP_AIR * flow_rate
|
||||||
|
return HV_inf
|
||||||
|
|
||||||
|
|
||||||
|
def ventilation_losses(rooms: list[Room], eta) -> float:
|
||||||
|
sum_wet = 0
|
||||||
|
sum_dry = 0
|
||||||
|
|
||||||
|
for room in rooms:
|
||||||
|
if room.is_wet:
|
||||||
|
sum_wet += room.flow_rate
|
||||||
|
else:
|
||||||
|
sum_dry += room.flow_rate
|
||||||
|
flow_rate = max(sum_dry, sum_wet) / 3600 # m^3 / s
|
||||||
|
HV_act = RHO_CP_AIR * flow_rate * (1 - eta)
|
||||||
|
return HV_act
|
||||||
|
|
||||||
|
|
||||||
|
def transmission_losses(interfaces: list[Interface]) -> float:
|
||||||
|
print(" - Transmission loss contribution by part:")
|
||||||
|
for interface in interfaces:
|
||||||
|
if isinstance(interface, Surface):
|
||||||
|
print(
|
||||||
|
f" - {interface.name:16s} U = {interface.U:4.2f} W/m²K HT = {interface.HT:4.1f} W/K"
|
||||||
|
)
|
||||||
|
HT = sum(interface.HT for interface in interfaces)
|
||||||
|
return HT
|
||||||
|
|
||||||
|
|
||||||
|
def report(situation) -> None:
|
||||||
|
name = situation["name"]
|
||||||
|
rooms = situation["ventilation_rooms"]
|
||||||
|
eta_vent = situation["ventilation_eta"]
|
||||||
|
infiltration_area = situation["ventilation_v50_area"]
|
||||||
|
infiltration_v50 = situation["ventilation_v50_value"]
|
||||||
|
|
||||||
|
interfaces = situation["transmission_interfaces"]
|
||||||
|
|
||||||
|
delta_t_worst = situation["environment_delta_t_worst"]
|
||||||
|
delta_t_typical = situation["environment_delta_t_typical"]
|
||||||
|
|
||||||
|
print(f"Report for situation: {name}")
|
||||||
|
|
||||||
|
HV_inf_worst = infiltration_losses(infiltration_area, infiltration_v50)
|
||||||
|
HV_inf_typical = infiltration_losses(
|
||||||
|
infiltration_area, infiltration_v50, reduction_factor=25
|
||||||
|
)
|
||||||
|
HV_act = ventilation_losses(rooms, eta_vent)
|
||||||
|
print(" - Ventilation loss contribution by part:")
|
||||||
|
HV_tot = HV_inf_worst + HV_act
|
||||||
|
HV_tot_typical = HV_act + HV_inf_typical
|
||||||
|
print(f" - Infiltration HV = {HV_inf_worst:4.1f} W/K")
|
||||||
|
print(f" - Active ventilation HV = {HV_act:4.1f} W/K")
|
||||||
|
|
||||||
|
HT = transmission_losses(interfaces)
|
||||||
|
|
||||||
|
P_worst = (HV_tot + HT) * delta_t_worst
|
||||||
|
# FIXME: hacky way to do a less dramatic worst case to consider
|
||||||
|
P_worst2 = (HV_tot + HT) * 23
|
||||||
|
P_typical = (HV_tot_typical + HT) * delta_t_typical
|
||||||
|
|
||||||
|
print(f" - HV = {HV_tot:7.1f} W/K")
|
||||||
|
print(f" - HT = {HT:7.1f} W/K")
|
||||||
|
print(f" - P worst = {P_worst:5.0f} W")
|
||||||
|
print(f" - P worst2 = {P_worst2:5.0f} W")
|
||||||
|
print(f" - P typical = {P_typical:5.0f} W")
|
||||||
Reference in New Issue